Jump to main content

n1-02: Hunting Prevention Gain Setting

No.

(Hex.)

Name

Description

Default

(Range)

n1-02

(0581)

Expert

Hunting Prevention Gain Setting

Sets the performance of the hunting prevention function. Usually it is not necessary to change this parameter.

1.00

(0.00 - 2.50)

Adjust this parameter in these conditions:

  • When n1-01 = 1 [Hunting Prevention Selection = Enabled (Normal)], if oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.

  • When n1-01 = 2, if the motor stalls, decrease the setting value in 0.1-unit increments.