Jump to main content

n2-01: Automatic Freq Regulator Gain

No.

(Hex.)

Name

Description

Default

(Range)

n2-01

(0584)

Automatic Freq Regulator Gain

Sets the gain of the AFR function as a magnification value. Usually it is not necessary to change this setting.

1.00

(0.00 - 10.00)

Adjust this parameter in these conditions:

  • If hunting or oscillation occurs with light loads, increase the setting value in 0.05-unit increments and examine the response.

  • When torque is not sufficient with heavy loads or to make the torque or speed response better, decrease the setting value in 0.05-unit increments and examine the response.