YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
n2-01
(0584)
Automatic Freq Regulator Gain
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to change this setting.
1.00
(0.00 - 10.00)
Adjust this parameter in these conditions:
If hunting or oscillation occurs with light loads, increase the setting value in 0.05-unit increments and examine the response.
When torque is not sufficient with heavy loads or to make the torque or speed response better, decrease the setting value in 0.05-unit increments and examine the response.