Jump to main content

n3-02: HSB Current Limit Level

No.

(Hex.)

Name

Description

Default

(Range)

n3-02

(0589)

Expert

HSB Current Limit Level

Sets the maximum current output during high-slip braking as a percentage, where E2-01 [Motor Rated Current (FLA)] is 100%. Also set the current suppression to prevent exceeding drive overload tolerance.

Determined by C6-01

(0 - 150%)

Note:

The upper limit to the setting range changes when the setting for C6-01 [Normal / Heavy Duty Selection] changes.

  • 150% when C6-01 = 0 [Heavy Duty Rating]

  • 120% when C6-01 = 1 [Normal Duty Rating]

When you decrease the setting value for current suppression, it will make the deceleration time longer.

  • When you must detect ov [DC Bus Overvoltage] during high-slip braking, set this parameter to a low value.

  • If the motor current increases during high-slip braking, decrease the setting value to prevent burn damage in the motor.

  • The overload tolerance for the drive is 150% for Heavy Duty Rating (HD) and 110% for Normal Duty Rating (ND).