No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L1-08
(1103)
|
oL1 Current Level
|
   
Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.
|
0.0 A
(0.0 A or 10% to 150% of the drive rated current)
|
When L1-08 = 0.0 A, the drive uses E2-01 [Motor Rated Current (FLA)] to detect the motor overload protection. In PM control mode, the drive uses E5-03 [PM Motor Rated Current (FLA)] to detect the motor overload protection.
When L1-08 ≠ 0.0 A, the set value is the reference for motor overload protection.
Note:
-
Display is in these units:
-
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
-
0.1 A: 2056 to 2082, 4031 to 4060
-
When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.