Jump to main content

L1-09: oL1 Current Level for Motor 2

No.

(Hex.)

Name

Description

Default

(Range)

L1-09

(1104)

oL1 Current Level for Motor 2

Sets the reference current for the motor 2 thermal overload detection. When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.

0.0 A

(0.0 A or 10 to150% of the drive rated current)

When L1-09 = 0.0 A, the drive uses E4-01 [Motor 2 Rated Current] to detect the motor overload protection.

When L1-09 ≠ 0.0 A, the set value is the reference for motor overload protection.

Note:
  • Display is in these units:

    • 0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023

    • 0.1 A: 2056 to 2082, 4031 to 4060

  • When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.