Jump to main content

L1-23: Leakage Current Filter Time2

No.

(Hex.)

Name

Description

Default

(Range)

L1-23

(0769)

RUN

Leakage Current Filter Time2

Sets the leakage current detection reduction filter time constant during acceleration/deceleration.

Determined by C6-02

(0.0 - 60.0 s)

Note:
  • You can set this parameter when C6-02 = B [Carrier Frequency Selection = Leakage Current Detection Reduction Rate PWM].

  • When the setting value increases, the current monitor will start up slowly. Examine the relevant sequence for problems.

If errors occur in the values on the current monitor during acceleration/deceleration, increase the setting value.