L2-02: Power Loss Ride Through Time

No.

(Hex.)

Name

Description

Default

(Range)

L2-02

(0486)

Power Loss Ride Through Time

Sets the length of time that the drive will wait before it tries to restart if the DC bus voltage is less than L2-05 [Undervoltage Detection Lvl (Uv1)] after a momentary power loss.

Determined by o2-04, C6-01

(0.0 - 25.5 s)

This function is applicable when L2-01 = 1, 3 [Power Loss Ride Through Select = Enabled, Kinetic Energy Backup: L2-02].

After a power loss, if these conditions are satisfied, the drive detects Uv1 [DC Bus Undervoltage], shuts off the output, and the motor coasts to stop:

  • After the DC bus voltage decreases less than the level of L2-05 [Undervoltage Detection Lvl (Uv1)], the time set in L2-02 is expired.

  • The drive does not detect a Uv2 [Control Power Undervoltage].

Depending on use conditions, if the time set in L2-02 is long, the drive may detect Uv2 before Uv1. If this is a problem, decrease the time set in L2-02 to prevent Uv2.

Note:
  • The length of time that the drive can recover after a power loss changes when drive capacity changes.

  • The upper limit of the possible momentary power loss Ride-Thru time changes when drive capacity changes.