No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L2-03
(0487)
|
Minimum Baseblock Time
|
   
Sets the minimum time to continue the drive output block (baseblock) after a baseblock.
|
Determined by o2-04, C6-01
(0.1 - 5.0 s)
|
Sets the length of time that the drive will wait for the residual voltage in the motor to dissipate in estimation to the secondary circuit time constant of the motor. If oC [Overcurrent] or ov [DC Bus Overvoltage] occur at the start of Speed Search, after power returns, or during DC Injection Braking, increase this setting.