L2-05: Undervoltage Detection Lvl (Uv1)

No.

(Hex.)

Name

Description

Default

(Range)

L2-05

(0489)

Undervoltage Detection Lvl (Uv1)

Sets the voltage at which a Uv1 [DC Bus Undervoltage] fault is triggered or at which the KEB function is activated. Usually it is not necessary to change this setting.

Determined by o2-04 and E1-01

(200 V Class: 150 - 210 V, 400 V Class: 300 - 420 V)

Note:

If the low voltage detection level is near the lower limit value of L2-05, the drive will detect Uv1 during KEB Ride-Thru operation. Do not set the value too low when you use the KEB Ride-Thru function.