L2-06: Kinetic Energy Backup Decel Time

No.

(Hex.)

Name

Description

Default

(Range)

L2-06

(048A)

Expert

Kinetic Energy Backup Decel Time

Sets the deceleration time during KEB operation used to decrease the maximum output frequency to 0.

0.0 s

(0.0 - 6000.0 s)

Set L2-29 = 2 or 3 [Kinetic Energy Backup Method = System KEB Ride-Thru 1 or System KEB Ride-Thru 2] to enable this function. When L2-29 = 1, 2 , 3 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2, System KEB Ride-Thru 1, System KEB Ride-Thru 2] and you do KEB Auto-Tuning, the drive will automatically set this value.

Sets the deceleration time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a momentary power loss. If a Uv1 [DC Bus Undervoltage] fault occurs during KEB operation, decrease the deceleration time. If an ov [Overvoltage] fault occurs, increase the deceleration time.

  • L2-06 = 0

    The drive automatically decreases C1-09 [Fast Stop Time] to the base value to keep the DC bus voltage above the low voltage detection level. The drive ignores L2-02 [Momentary Power Loss Ride-Thru Time] in this condition.

  • L2-06 ≠ 0

    As shown in Figure 1, the frequency reference decelerates to the KEB frequency level as specified by the deceleration rate set in L2-06 and then returns to the initial frequency reference as specified by C1-01 [Acceleration Time 1]. The drive uses the setting value of the KEB frequency rate as shown in the this formula to set the KEB frequency level:

    KEB frequency level = Output frequency before power loss × (1 - (L2-02)/ (L2-06))

Figure 1. Kinetic Energy Backup Decel Time