YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L2-09
(048D)
Expert
KEB Minimum Frequency Level
Sets the quantity of output frequency reduction used as a percentage of E2-02 [Motor Rated Slip] when KEB operation starts.
20%
(0 - 100%)
These conditions set the quantity of decrease:
Motor rated slip × (L2-09/100)
The larger value between the value calculated with L2-08 and the value calculated with L2-09