Jump to main content

L2-30: KEB Zero Speed Operation

No.

(Hex.)

Name

Description

Default

(Range)

L2-30

(045E)

Expert

KEB Zero Speed Operation

Sets the operation when the output frequency decreases below the zero level (DC braking injection starting frequency) during KEB deceleration when L2-01 = 3 to 5 [Power Loss Ride Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU Power, or Kinetic Energy Backup: DecelStop].

0

(0, 1)

0
Baseblock
 
1
DC/SC Braking