L3-03: Stall Prevent Limit during Accel

No.

(Hex.)

Name

Description

Default

(Range)

L3-03

(0491)

Stall Prevent Limit during Accel

Sets the lower limit for the stall prevention level used in the constant output range as a percentage of the drive rated output current.

50%

(0 - 100%)

The stall prevention level set in L3-02 [Stall Prevent Level during Accel] is automatically reduced when the motor is running within the constant output range. Parameter L3-03 is the limit value used to prevent the stall prevention level during constant output ranges to fall below the minimum required level.

Note:

The function to automatically reduce the stall prevention level does not operate when L3-01 = 3 [Stall Prevention during Accel = Current Limit Method].

Figure 1. Stall Prevent Level during Accel/Limit