L3-06: Stall Prevent Level during Run

No.

(Hex.)

Name

Description

Default

(Range)

L3-06

(0494)

Stall Prevent Level during Run

Sets the output current level at which the Stall Prevention function is enabled during run when the drive rated output current is 100%.

Determined by C6-01

(5 - 150%)

Note:
  • This parameter is applicable when L3-05 = 1, 2 [Stall Prevention during RUN = Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-04)].

  • When L3-23 = 1 [Stall P Reduction at Constant HP = Automatic Reduction @ CHP Region], the drive will automatically decrease the level in the constant output range.

  • The upper limit to the setting range changes when the setting for C6-01 [Normal / Heavy Duty Selection] changes.

    • 150% when C6-01 = 0 [Heavy Duty Rating]

    • 120% when C6-01 = 1 [Normal Duty Rating]

Use an Analog Input to Change the Stall Prevent Level during Run

When H3-xx = 8 [MFAI Function Select = Stall Prevent Level During Run], you can use the input gain and bias settings for terminals A1 and A2 to change the stall prevention level during run.

If you set the input level for terminals A1 and A2 [H3-xx = 8] and L3-06, the drive will use the smaller value for Stall Prevent Level during Run.

Figure 1. Stall Prevention Level during Run with Analog Input