No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L3-17
(0462)
|
DC Bus Regulation Level
|
   
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel Stall Prevention function (Intelligent Stall Prevention) are active.
|
200 V Class: 375 V,
400 V Class: 750 V
(200 V Class: 150 to 400 V, 400 V Class: 300 to 800 V)
|
Note:
This value is initialized when E1-01 [Input AC Supply Voltage] is changed.
Sets this parameter for any of the following circumstances.