YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L3-20
(0465)
Expert
DC Bus Voltage Adjustment Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
Set one of these parameters to enable L3-20:
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
If stall prevention during deceleration function causes ov [Overvoltage] and Uv1 [DC Bus Undervoltage] faults when you start deceleration and L2-29 = 1, H1-xx = 7A or 7B, or L3-04 = 2, gradually increase this parameter in 0.1-unit increments. If the setting value is too high, it can cause large speed or current ripples.
If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If the setting value is too high, it can cause large speed or current ripples.