No.
(Hex.)
|
Name
|
Description
|
Default
(Range)
|
|
L3-36
(11D0)
|
Current Suppression Gain@Accel
|
   
Sets the gain to suppress current and motor speed hunting during operation when L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]. Usually it is not necessary to change this setting.
|
Determined by A1-02
(0.0 - 100.0)
|
If there is vibration in the output current during acceleration, increase the setting value.
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.