YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L4-08
(047F)
Speed Agree Source Selection
Sets the drive to use the soft starter output frequency or the motor speed (estimation value) for speed detection.
0
(0, 1)
The setting for L4-08 has an effect:
When you set detection conditions for oL3 [Overtorque 1], oL3 [Overtorque Detection 1], oL4 [Overtorque 2], and oL4 [Overtorque Detection 2]:
L6-01 = 1, 3, 5, 7 [Torque Detection Selection 1 = UL @ Speed Agree]
L6-04 = 1, 3, 5, 7 [Torque Detection Selection 2 = UL @ Speed Agree]
When you use speed agreement with DriveWorksEZ.
When the MFDI terminals set for H1-xx = 75, 76 [Up/Down 2 command] activate.
When you set H2-xx [MFDO Function Select] to these functions:
Setting Value
Function
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
When you use these functions for MEMOBUS monitor data:
Register No.
002CH
Drive Status 2
bit2
Speed agreement
1: During agreement
bit3
User-defined speed agreement
bit4
1: Output frequency ≤ L4-01
bit5
1: Output frequency ≥ L4-01
004BH
U1-12 [Drive Status]
1: During speed agreement
When you use these functions for monitor parameters:
U1-12
(004B)
Drive Status
bit 4: During speed agreement