Jump to main content

L4-08: Speed Agree Source Selection

No.

(Hex.)

Name

Description

Default

(Range)

L4-08

(047F)

Speed Agree Source Selection

Sets the drive to use the soft starter output frequency or the motor speed (estimation value) for speed detection.

0

(0, 1)

0
Softstarter Output (Reference)
 
1
Motor Speed (Actual Speed)
 

The setting for L4-08 has an effect:

  • When you set detection conditions for oL3 [Overtorque 1], oL3 [Overtorque Detection 1], oL4 [Overtorque 2], and oL4 [Overtorque Detection 2]:

    • L6-01 = 1, 3, 5, 7 [Torque Detection Selection 1 = UL @ Speed Agree]

    • L6-04 = 1, 3, 5, 7 [Torque Detection Selection 2 = UL @ Speed Agree]

  • When you use speed agreement with DriveWorksEZ.

  • When the MFDI terminals set for H1-xx = 75, 76 [Up/Down 2 command] activate.

  • When you set H2-xx [MFDO Function Select] to these functions:

     

    Setting Value

    Function

    2

    Speed Agree 1

    3

    User-Set Speed Agree 1

    4

    Frequency Detection 1

    5

    Frequency Detection 2

    13

    Speed Agree 2

    14

    User-Set Speed Agree 2

    15

    Frequency Detection 3

    16

    Frequency Detection 4

  • When you use these functions for MEMOBUS monitor data:

     

    Register No.

    Description

    002CH

    Drive Status 2

    bit2

    Speed agreement

    1: During agreement

    bit3

    User-defined speed agreement

    1: During agreement

    bit4

    Frequency Detection 1

    1: Output frequency ≤ L4-01

    bit5

    Frequency Detection 2

    1: Output frequency ≥ L4-01

    004BH

    U1-12 [Drive Status]

    bit4

    1: During speed agreement

  • When you use these functions for monitor parameters:

     

    No.

    (Hex.)

    Name

    Description

    U1-12

    (004B)

    Drive Status

    bit 4: During speed agreement