Jump to main content

L6-02: Torque Detection Level 1

No.

(Hex.)

Name

Description

Default

(Range)

L6-02

(04A2)

Torque Detection Level 1

Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output current = 100% value. In vector control, motor rated torque = 100% value.

150%

(0 - 300%)

Note:
  • Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening detection level.

  • You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = 7 [MFAI Function Select = Overtorque/Undertorque DetectLvl]. If you set L6-02 and H3-x = 7, the analog input is most important and the drive disables L6-02.