1
|
Multi-step speed reference
|
0.00
|
0
|
0
|
-
When the Up 2 Command is active, the drive accelerates the motor (increases the bias value).
-
When the Down 2 Command is active, the drive decelerates the motor (decreases the bias value)
-
When the Up 2 Command and Down 2 Command are active or not active, the drive holds the output frequency. (holds the bias value).
-
When the frequency changes, it will reset the bias.
-
For all other statuses, the drive will follow the frequency reference.
|
Not stored.
|
|
2
|
1
|
When the bias value and frequency reference are constant for 5 seconds after the frequency reference hold starts, the drive will add the bias value to the enabled frequency reference, then reset.
|
|
3
|
1
|
-
|
-
When the Up 2 Command is active, the drive accelerates the motor.
-
When the Down 2 Command is active, the drive decelerates the motor.
-
For all other statuses, the drive will follow the frequency reference.
|
Not stored.
|
|
4
|
Multi-step speed reference
|
> 0
|
-
|
0
|
-
When the Up 2 Command is active, the drive accelerates the motor to “Frequency Reference + d4-03” (the bias value will increase to the value set in d4-03)
-
When the Down 2 Command is active, the drive decelerates the motor to “Frequency Reference - d4-03” (the bias value will decrease to the value set in d4-03).
-
When the Up 2 Command and Down 2 Command are active or not active, the drive holds the output frequency. (holds the bias value).
-
When the frequency changes, it will reset the bias.
-
For all other statuses, the drive will follow the frequency reference.
|
Not stored.
|
|
5
|
1
|
When the bias value and frequency reference are constant for 5 seconds after the frequency reference hold starts, the drive will add the bias value to the enabled frequency reference, then reset.
|
|
6
|
Others
(Analog input, transmission)
|
0
|
0
|
0
|
-
When the Up 2 Command is active, the drive accelerates the motor (increases the bias value).
-
When the Down 2 Command is active, the drive decelerates the motor (decreases the bias value)
-
When the Up 2 Command and Down 2 Command are active or not active, the drive holds the output frequency (holds the bias value).
-
During acceleration or deceleration, when the frequency reference increases or decreases more than d4-07, the drive holds the bias value until the output frequency and the actual frequency reference agree (speed agreement).
|
Not stored.
|
|
7
|
1
|
When the bias value is constant for 5 seconds after the frequency reference hold starts, the drive will store the bias value in d4-06. You cannot rewrite the frequency reference is not possible. The drive will store only the bias value.
|
|
8
|
Others
(Analog input, transmission)
|
0
|
1
|
-
|
-
When the Up 2 Command is active, the drive accelerates the motor (increases the bias value).
-
When the Down 2 Command is active, the drive decelerates the motor (decreases the bias value)
-
For all other statuses, the drive will follow the frequency reference.
|
Not stored.
|
|
9
|
> 0
|
-
|
0
|
-
When the Up 2 Command is active, the drive accelerates the motor to “Frequency Reference + d4-03” (the bias value will increase to the value set in d4-03)
-
When the Down 2 Command is active, the drive decelerates the motor to “Frequency Reference - d4-03” (the bias value will decrease to the value set in d4-03).
-
During acceleration or deceleration, when the frequency reference increases or decreases more than d4-07, the drive holds the bias value until the output frequency and the actual frequency reference agree (speed agreement).
|
Not stored.
|
|
10
|
1
|
When the bias value is constant for 5 seconds after the frequency reference hold starts, the drive will store the bias value in d4-06. You cannot rewrite the frequency reference is not possible. The drive will store only the bias value.
|