H2-06: Watt Hour Output Unit Selection

No.

(Hex.)

Name

Description

Default

(Range)

H2-06

(0437)

Watt Hour Output Unit Selection

Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt Hour Pulse Output].

0

(0 - 4)

This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. The drive triggers a 200 ms pulse each time the KWh data is at the value set in H2-06. This parameter sets the kWh unit for each pulse output.

Figure 1. Example MFDO when Configured for Watt Hours
Note:
  • When the power value is a negative value (regenerative state), the drive does not count Watt hours.

  • When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive to lose control power, the Watt hour count will reset.

0
0.1 kWh units
 
1
1 kWh units
 
2
10 kWh units
 
3
100 kWh units
 
4
1000 kWh units