2: Speed Agree 1

Setting Value

Function

Description

2

Speed Agree 1

The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].

Note:

The detection function operates in the two motor rotation directions.

Figure 1. Speed Agree 1 Time Chart
ON
The output frequency is in the range of “frequency reference ± L4-02”.
 
OFF
The output frequency does not align with the frequency reference although the drive is running.