|
Setting Value
|
Function
|
Description
|
|
4
|
Frequency Detection 1
|
   
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection Width]. After the terminal deactivates, the terminal stays deactivated until the output frequency = L4-01.
|
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
- ON
- The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 + L4-02.
-
- OFF
- The output frequency is higher than the value of L4-01 + L4-02.
-
Figure 1. Frequency Detection 1 Time Chart
Note:
Figure 1 shows the result of the configuration when L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]. The default setting of L4-07 is 0 [No detection during baseblock]. When the speed agreement detection selection is “No Detection during Baseblock”, the terminal is deactivated when the drive output stops.