L7-02: Reverse Torque Limit

No.

(Hex.)

Name

Description

Default

(Range)

L7-02

(04A8)

RUN

Reverse Torque Limit

Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the 100% value.

200%

(0 - 300%)

Note:
  • The lower torque limit is enabled when you set the torque limit by the following method.

    • Set H3-02 or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].

    • Use a communication option to set the torque limits

  • You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC [Overcurrent].

  • If you set the value too low with large loads, the motor can stall.