L7-04: Reverse Regenerative Trq Limit

No.

(Hex.)

Name

Description

Default

(Range)

L7-04

(04AA)

RUN

Reverse Regenerative Trq Limit

Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated torque.

200%

(0 - 300%)

Note:
  • Use this method to set the torque limit and enable the lower torque limit:

    • Set H3-02 or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].

    • Use a communication option to set the torque limits

  • You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC [Overcurrent].

  • If you set the value too low with large loads, the motor can stall.