Jump to main content

n6-05: Online Tuning Gain

No.

(Hex.)

Name

Description

Default

(Range)

n6-05

(05C7)

Expert

Online Tuning Gain

Sets the compensation gain when n6-01 = 2 [Online Tuning Selection = Voltage Correction Tuning]. Usually it is not necessary to change this parameter.

1.0

(0.1 - 50.0)

When you use a motor that has a large secondary circuit time constant, decrease the setting value.

If the drive detects oL1 [Motor Overload], increase the setting value in 0.1-unit increments.