Jump to main content

L8-02: Overheat Alarm Level

No.

(Hex.)

Name

Description

Default

(Range)

L8-02

(04AE)

Overheat Alarm Level

Sets the oH detection level in temperature.

Determined by o2-04, C6-01

(50 - 150 °C)

If the heatsink temperature is more than the temperature set in this parameter, the drive detects an overheat pre-alarm. To enable this function, set one of H2-01 to H2-03 [MFDO Function Select] to 20 [Drive Overheat Pre-Alarm (oH)].

If the temperature increases to the overheat fault level, the drive will trigger an oH1 [Heatsink Overheat] fault and stop operation.