YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
L8-05
(04B1)
Input Phase Loss Protection Sel
Sets the function to enable and disable input phase loss detection.
0
(Determined by o2-04)
The drive measures ripples in DC bus voltage to detect input phase loss.
The drive detects phase loss when power supply phase loss occurs or the main circuit capacitor becomes unusable, which causes PF [Input Phase Loss] to show on the keypad.
Disable the detection of the input power supply phase loss function in these conditions:
During deceleration
The run command is not input
The output current is less than 30% of the drive rated current.