YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
n7-10
(311A)
Expert
Pull-in Current Switching Speed
Sets the speed range to operate with the pull-in current command. Drive rated frequency = 100% value. If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
10.0%
(0.0 - 100.0%)
When the drive accelerates, it enables these settings:
Motor speed ≤ n7-10 + n7-11 [Drv Mode Switch Hysteresis Band]: n8-51 [Pull-in Current @ Acceleration]
Motor speed > n7-10 + n7-11: b8-01 [Energy Saving Control Selection]
When the drive decelerates, it enables these settings:
Motor speed ≤ n7-10: n8-51 [Pull-in Current @ Acceleration]
Motor speed > n7-10: b8-01 [Energy Saving Control Selection]
If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
When it is most important to save energy in the low speed range, decrease the setting value.