L8-10: Heatsink Fan Operation Selection

No.

(Hex.)

Name

Description

Default

(Range)

L8-10

(04B6)

Heatsink Fan Operation Selection

Sets operation of the heatsink cooling fan.

0

(0 - 2)

0
During Run, w/ L8-11 Off-Delay

The drive turns on the fan when a Run command is active.

When you release the Run command and the delay time set in L8-11 [Heatsink Fan Off-Delay Time] is expired, the fan stops. This setting extends the fan lifetime.

1
Always On

The fan turns on when you supply power to the drive.

2
Temperature-Dependent Fan Ctrl.

The fan turns on when the drive detects that the main circuit is overheating.