YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
n7-17
(3122)
Resistance TemperatureCorrection
Sets the function to adjust for changes in the motor resistance value caused by changes in the temperature.
1
(0 to 2)
For settings 1 and 2, the adjustment time can cause a delay before startup.
For settings 1 and 2, the drive can set the line-to-line resistance value of E9-10 [Motor Line-to-Line Resistance].
When the temperature will change at startup, use setting 2.
To decrease the startup time, set this parameter to 0, then do line-to-line resistance tuning.
If you will start from coasting, set this parameter to 0, then do line-to-line resistance tuning.