Jump to main content

L8-31: LF2 Detection Time

No.

(Hex.)

Name

Description

Default

(Range)

L8-31

(04E1)

LF2 Detection Time

Sets the LF2 [Output Current Imbalance] detection time.

3

(1 – 100)

When the output current is unbalanced for longer than the time set in L8-31, the drive detects LF2.

Note:
  • Set L8-29 = 1 [Output Unbalance Detection Sel = Enabled] to enable L8-31.

  • If the drive incorrectly detects LF2, increase L8-31 in 5-unit increments.

  • The keypad shows L8-31 when E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)] in EZ Vector Control.