L8-40: Carrier Freq Reduction Off-Delay

No.

(Hex.)

Name

Description

Default

(Range)

L8-40

(04F1)

Carrier Freq Reduction Off-Delay

Sets the length of time until the automatically reduced carrier frequency returns to the condition before the reduction.

Determined by A1-02

(0.00 - 2.00 s)

Set L8-40 ≠ 0.00 to enable the carrier frequency reduction function during start-up. When operation starts, the drive automatically decreases the carrier frequency. When the time set in L8-40 is expired, the carrier frequency returns to the value set in C6-02 [Carrier Frequency Selection].