YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
n8-47
(053A)
Pull-in Current Comp Filter Time
Sets the time constant the drive uses to align the pull-in current reference value with the actual current value. Usually it is not necessary to change this setting.
5.0 s
(0.0 - 100.0 s)
Adjust this parameter in these conditions:
If the time for the reference value of the pull-in current to align with the target value is too long, increase the setting value.
If vibration or hunting occur, decrease the setting value in 0.2 unit increments.
If the motor stalls during run at constant speed, decrease the setting value in 0.2 unit increments.