Jump to main content

n8-47: Pull-in Current Comp Filter Time

No.

(Hex.)

Name

Description

Default

(Range)

n8-47

(053A)

Pull-in Current Comp Filter Time

Sets the time constant the drive uses to align the pull-in current reference value with the actual current value. Usually it is not necessary to change this setting.

5.0 s

(0.0 - 100.0 s)

Adjust this parameter in these conditions:

  • If the time for the reference value of the pull-in current to align with the target value is too long, increase the setting value.

  • If vibration or hunting occur, decrease the setting value in 0.2 unit increments.

  • If the motor stalls during run at constant speed, decrease the setting value in 0.2 unit increments.