T2-02: PM Motor Code Selection

No.

(Hex.)

Name

Description

Default

(Range)

T2-02

(0751)

PM Motor Code Selection

If the drive is operating an SMRD, SMRA, or SSR1 series Yaskawa PM motor, enter the PM motor code in to align with the rotation speed and motor output.

Determined by A1-02 and o2-04

(0000 - FFFF)

Enter the motor code to automatically set parameters T2-03 to T2-14. When you are operating a specialized motor or a non-Yaskawa motor, set T2-02 = FFFF and enter the data from the motor nameplate or the motor test report.

You can only enter the permitted PM motor codes. Different drive control methods will accept different PM motor codes.