YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
o1-03
(0502)
Frequency Display Unit Selection
Sets the display units for the frequency reference and output frequency.
Determined by A1-02
(0 - 3)
Select the setting unit of these parameters:
d1-01 to d1-17 [Reference 1 to 17]
U1-01 [Frequency Reference]
U1-02 [Output Frequency]
U1-05 [Motor Speed]
U1-16 [SFS Output Frequency]
U4-14 [PeakHold Output Freq]
For monitor 2, the setting value is always 0 [Hz Unit].
The maximum output frequency is 100%.
The drive uses the maximum output frequency and number of motor poles to calculate this value automatically.
When you set o1-03 = 2 [min-1 (r/min) units], make sure that you set the number of motor poles in these parameters:
E2-04 [Motor Pole Count]
E4-04 [Motor 2 Motor Poles]
E5-04 [PM Motor Pole Count]
E9-08 [Number of Poles]
Uses o1-10 and o1-11 to set the unit of measure. The value of parameter o1-10 is the value when you remove the decimal point from the maximum output frequency. Parameter o1-11 is to the number of digits after the decimal point in the maximum output frequency.
To display a maximum output frequency of 100.00, set parameters to these values:
o1-10 = 10000
o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]