o4-24

(310F)

RUN

bAT Detection Selection

Sets the operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM [Keypad Time Not Set]. This parameter is only available when you use an LCD keypad.

0

(0 - 2)

0
Disable

The drive will not detect bAT or TiM.

1
Enable (Alarm Detected)

The keypad shows bAT or TiM and the drive continues operation. The output terminal set to Alarm [H2-01 to H2-03 = 10] activates.

2
Enable (Fault Detected)