H5-04
(0428)
Communication Error Stop Method
Sets the motor Stopping Method when the drive detects CE [MEMOBUS/Modbus Communication Err] issues.
3
(0 - 3)
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault [H2-01 to H2-03 = E] activates.
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E] activates.
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault [H2-01 to H2-03 = E] activates.
The keypad shows CE and the drive continues operation. The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.