H5-05: Comm Fault Detection Selection

No.

(Hex.)

Name

Description

Default

(Range)

H5-05

(0429)

Comm Fault Detection Selection

Sets the function that detects CE [Modbus Communication Error] issues during MEMOBUS/Modbus communications.

1

(0, 1)

If the drive does not receive data from the master during the time set in H5-09 [CE Detection Time], it will detect a CE error.

0
Disabled

Does not detect CE. The drive continues operation.

1
Enabled

Detects CE. If the drive detects CE, it will operate as specified by the setting of H5-04 [Communication Error Stop Method].