YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
H6-06
(0431)
RUN
Terminal MP Monitor Selection
Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx monitor.
102
(000, 031, 101, 102, 105, 116, 501, 502, 801 - 809, 821 - 825, 831 - 839, 851 - 855)
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
Use the pulse train monitor as the sourcing output.
Output Voltage
VRL(V)
Load Impedance (kΩ)
5 V or more
1.5 kΩ or more
8 V or more
4.0 kΩ or more
10 V or more
10 kΩ or more
Use the pulse train monitor as the sinking input
External Power Supply (V)
12 VDC ± 10%, 15 VDC ± 10%
Sinking current (mA)
16 mA or less