H6-06: Terminal MP Monitor Selection

No.

(Hex.)

Name

Description

Default

(Range)

H6-06

(0431)

RUN

Terminal MP Monitor Selection

Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx monitor.

102

(000, 031, 101, 102, 105, 116, 501, 502, 801 - 809, 821 - 825, 831 - 839, 851 - 855)

Note:

To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.

When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load conditions:

Incorrect connections can make the characteristics not sufficient or cause mechanical damage.

  • Use the pulse train monitor as the sourcing output.

     

    Output Voltage

    VRL(V)

    Load Impedance (kΩ)

    5 V or more

    1.5 kΩ or more

    8 V or more

    4.0 kΩ or more

    10 V or more

    10 kΩ or more

    Figure 1. Circuit Diagram When Used as the Sourcing Output
  • Use the pulse train monitor as the sinking input

     

    External Power Supply (V)

    12 VDC ± 10%, 15 VDC ± 10%

    Sinking current (mA)

    16 mA or less

    Figure 2. Circuit Diagram When Used as the Sinking Input