MEMOBUS/Modbus MFAI 1 to 3 Function Selection

You can set the MFAI function to MEMOBUS/Modbus register15C1 to 15C3 (Hex.) [Mbus Reg 15C1h through 15C3h Input Function]. Use H3-40 to H3-42 [Mbus Reg 15C1h through 15C3h Input Function] to set the function for each register and use H3-43 [Mbus Reg Inputs FilterTime Const] to set the input filter.

Table 1. MEMOBUS Multi-Function AI Command Register

Register number

(Hex.)

Name

Range 1

Parameter

15C1

Mbus Reg 15C1h Input Function

-32767 to +32767

H3-40

15C2

Mbus Reg 15C2h Input Function

-32767 to +32767

H3-41

15C3

Mbus Reg 15C3h Input Function

-32767 to +32767

H3-42

 
Figure 1. Functional Block Diagram for MEMOBUS Multi-Function AI Command 1
Note:
  • Refer to Multi-Function Analog Input Terminal Settings for the analog input setting values.

  • When you will not use the terminal, set H3-40 to H3-42 = F. Parameters H3-40 to H3-42 do not support the through mode.

  • You cannot use H3-40 to H3-42 to set these MFAI functions:

     

    H3-xx Setting Value

    Function

    0

    Frequency Reference

    1

    Frequency Gain

    2

    Auxiliary Frequency Reference 1

    3

    Auxiliary Frequency Reference 2

    30

    DWEZ Analog Input 1

    31

    DWEZ Analog Input 2

1

Set as 100% = 4096.