Jump to main content

H3-03: Terminal A1 Gain Setting

No.

(Hex.)

Name

Description

Default

(Range)

H3-03

(0411)

RUN

Terminal A1 Gain Setting

Sets the gain of the analog signal input to MFAI terminal A1.

100.0%

(-999.9 - +999.9%)

This parameter sets the quantity of reference for the function set for terminal A1 as a percentage when 10 V (or 20 mA) is input.

Use this parameter and H3-04 [Terminal A1 Bias Setting] to adjust the characteristics of the analog input signal to terminal A1.