H3-14: Analog Input Terminal Enable Sel

No.

(Hex.)

Name

Description

Default

(Range)

H3-14

(041C)

Analog Input Terminal Enable Sel

Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is ON.

7

(1, 2, 7)

Input signals do not have an effect on terminals not set as targets.

1
Terminal A1 only
 
2
Terminal A2 only
 
7
Terminals A1 and A2
 
Note:
  • The ON/OFF operation of terminal Sx set in Analog Terminal Input Selection [H1-xx = C] has an effect on only the analog input terminal selected with H3-14.

  • When H1-xx ≠ C, the functions set to terminals A1 and A2 are always enabled.