H3-17: Terminal A2 Offset

No.

(Hex.)

Name

Description

Default

(Range)

H3-17

(02F1)

Terminal A2 Offset

Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this setting.

0

(-500 - +500)

Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0 V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA [H3-09 = 3] is input.