YASKAWA AC Drive GA700 High Performance Type Technical Manual
Setting Value
Function
Description
16
Frequency Detection 4
The terminal activates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level(+/-)]. After the terminal activates, the terminal stays activated until the output frequency = L4-03 - L4-04.
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.