Jump to main content

b3-31: Spd Search Current Reference Lvl

No.

(Hex.)

Name

Description

Default

(Range)

b3-31

(0BC0)

Expert

Spd Search Current Reference Lvl

Sets the current level that decreases the output current during Current Detection Speed Search.

1.50

(1.50 - 3.50)

Set this parameter as a ratio of E2-03 [Motor No-Load Current]. The setting is a ratio with respect to 30% of the motor rated current when E2-03E2-01 [Motor Rated Current (FLA)] × 0.3.

Note:

When A1-02 = 8 [Control Method Selection = EZOLV], the setting is a ratio with respect to E9-06 [Motor Rated Current (FLA)] × 0.5.