The virtual I/O function performs the following.

  • Inputs the result of the output from the MFDO terminal to the MFDI terminal without external wiring.

  • Inputs the result of the output from the MFAO terminal to the MFAI terminal without external wiring.

Figure 1. Virtual Analog I/O Functional Block Diagram
Figure 2. Virtual Digital I/O Functional Block Diagram
Note:
  • Refer to MFDI Setting Values for more information on the virtual digital input functions.

  • Refer to MFDO Setting Values for more information on the virtual digital output functions.

  • Refer to Multi-Function Analog Input Terminal Settings for more information on the virtual analog input functions.

  • Refer to H4: Analog Outputs for more information on the virtual analog output functions.

  • You cannot set 0 [3-Wire Sequence] and 20 or 2F [External Fault] to H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4].

  • If you do not use virtual I/O, set H7-01 to H7-04 = F. This does not support the through mode.