Use terminal A2 to input a voltage or a current signal. Set the signal type as shown in Table 1.

Figure 1. Location of DIP Switch S1
Table 1. MFAI Terminal A2 Signal Settings

Terminal

Input Signal

DIP Switch Settings

Parameter

Switch

Setting

No.

Signal Level

A2

Current input

S1

I

(Default)

H3-09

2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)

3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)

Voltage input

V

0: 0 V to 10 V/0% to 100% (with zero limit) (input impedance: 20 kΩ)

1: 0 V to 10 V/0% to 100% (without zero limit) (input impedance: 20 kΩ)

Note:

Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.