Set the signal type for terminal AM to voltage or current output. Use jumper S5 and H4-07 [Terminal AM Signal Level Select] to set the signal type.

Figure 1. Location of Jumper Switch S5
 

Terminal

Types of Output Signals

Jumper S5

Parameter

No.

Signal Level

AM

Voltage output

(Default)

H4-07

0: 0 V to 10 V

Current output

2: 4 mA to 20 mA