This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
| Warning |
|
Fire Hazard
Do not connect main power supply wiring to drive motor terminals U/T1, V/T2, and W/T3. Connect main power supply wiring to main circuit input terminals R/L1, S/L2, and T/L3.
Incorrect wiring can cause serious injury or death from fire.
|
| Warning |
|
Sudden Movement Hazard
Make sure that you align the phase order for the drive and motor when you connect the motor to drive output terminals U/T1, V/T2, and W/T3.
If the phase order is incorrect, it can cause the motor to run in reverse. If the motor accidentally runs in reverse, it can cause serious injury or death.
|
| Notice |
|
Do not connect phase-advancing capacitors, LC/RC noise filters, or leakage breakers (ELCB) to the motor circuit.
If you connect these devices to the output circuits, it can cause damage to the drive and connected equipment.
|